Remote Air Cooled - CRA Series 10 HP TO 200 HP |
|
|
|
 |
Remote Air Cooled Chiller System The CRA Series is designed for new applications and the retrofit market.
CRA Series allows the air cooled condenser to be remotely installed. Utilizing proven, efficient, core components we offer a system with Glycol/Water Storage Tank and dedicated Glycol/Water Process Pump to circulate to the processing plant. |
|
· Large Size Range– The CRA Series is offered in various sizes from 10 HP
to 100 HP in multiple compressor configurations.
· Spiral Drum Heat Exchanger– Each model is supplied standard with the proven Spiral Drum Heat Exchanger. Combining the highest efficiency with unmatched durability. The Spiral Drum Evaporator is supplied with a 5 year replacement warranty
· Horizon™ Circuited Condenser– Supplied with or without our standard Horizon™ Circuited Condensers. The Finned Receiver and Subcooling Circuits deliver one of the most efficient condensers available
· CR110 Microprocessor Controller– The optional CR110 Controller can be installed on each model. Independent Control Cards provide improved Compressor, Condenser, Evaporator, and Pump Control. Multiple Cards can sbe connected to a common G55 hand held or panel mount interface device.
· Stainless Steel Glycol Pumps– System supplied standard with an internal Chiller Evaporator Pump and a Dedicated Glycol Process Pump. |
 |
 |
|
SINGLE COMPRESSOR SYSTEMS MINIMUM CIRCUIT AMPACITY
| REMOTE AIR COOLED CHILLER SYSTEM |
MODEL |
CAPACITY 28°F GLYCOL 110°F COND 10°F SUBCOOL |
CAPACITY 33°F GLYCOL 110°F COND 10°F SUBCOOL |
PROCESS PUMP |
TANK CAPACITY (GAL) |
DIMENSIONS L X W X H (INCHES) |
208-230V /3PH /60HZ |
460V /3PH /60HZ |
CONNECTIONS SIZES |
| 10 HP |
PB110F3R4250-R |
75,900 |
86,400 |
3 HP |
250 |
134 X 48 X 70 |
68 Amps |
34 Amps |
Supply & Return Connections are 2 Inch |
| 20 HP |
PB120F5R4250-R |
127,400 |
145,000 |
3 HP |
250 |
170 X 48 X 70 |
93 Amps |
46 Amps |
| 30 HP |
PB130F7R4250-R |
192,100 |
217,000 |
3 HP |
250 |
170 X 48 X 70 |
141 Amps |
69 Amps |
| 40 HP |
PB140F10R4250-R |
288,000 |
325,000 |
3 HP |
250 |
218 X 48 X 70 |
211 Amps |
105 Amps |
| 50 HP |
PB150F14R4250-R |
341,000 |
386,000 |
5 HP |
250 |
228 X 48 X 70 |
254 Amps |
127 Amps |
DUAL COMPRESSOR SYSTEMS MINIMUM CIRCUIT AMPACITY
| REMOTE AIR COOLED CHILLER SYSTEM |
MODEL |
CAPACITY 28°F GLYCOL 110°F COND 10°F SUBCOOL |
CAPACITY 33°F GLYCOL 110°F COND 10°F SUBCOOL |
PROCESS PUMP |
TANK CAPACITY (GAL) |
DIMENSIONS L X W X H (INCHES) |
208-230V /3PH /60HZ |
460V /3PH /60HZ |
GLYCOL FITTING CONNECTION SIZES |
| 20 HP |
PB210F6R4400-R |
151,800 |
172,800 |
5 HP |
400 |
148 X 94 X 70 |
122 Amps |
61 Amps |
Supply & Return Connections are 2 Inch |
| 40 HP |
PB220F10R4400-R |
254,800 |
290,000 |
5 HP |
400 |
184 X 94 X 70 |
169 Amps |
84 Amps |
| 60 HP |
PB230F14R4400-R |
384,200 |
434,000 |
7.5 HP |
400 |
184 X 94 X 70 |
257 Amps |
126 Amps |
| 80 HP |
PB240F20R4400-R |
576,000 |
650,000 |
7.5 HP |
400 |
232 X 94 X 70 |
384 Amps |
192 Amps |
| 100 HP |
PB250F28R4400-R |
682,000 |
772,000 |
7.5 HP |
400 |
234 X 94 X 70 |
456 Amps |
228 Amps |
TRIPLE COMPRESSOR SYSTEMS MINIMUM CIRCUIT AMPACITY
| REMOTE AIR COOLED CHILLER SYSTEM |
MODEL |
CAPACITY 28°F GLYCOL 110°F COND 10°F SUBCOOL |
CAPACITY 33°F GLYCOL 110°F COND 10°F SUBCOOL |
PROCESS PUMP |
TANK CAPACITY (GAL) |
DIMENSIONS L X W X H (INCHES) |
208-230V /3PH /60HZ |
460V /3PH /60HZ |
GLYCOL FITTING CONNECTION SIZES |
| 90 HP |
PB330F21R4400-R |
576,300 |
651,000 |
7.5 HP |
400 |
184 X 94 X 86 |
364 Amps |
182 Amps |
Supply & Return Connections are 2 Inch |
| 120 HP |
PB340F30R4400-R |
864,000 |
975,000 |
7.5 HP |
400 |
227 X 94 X 86 |
549 Amps |
275 Amps |
| 150 HP |
PB350F42R4400-R |
1,023,000 |
1,158,000 |
7.5 HP |
400 |
234 X 94 X 86 |
653 Amps |
326 Amps |
QUAD COMPRESSOR SYSTEMS MINIMUM CIRCUIT AMPACITY
| REMOTE AIR COOLED CHILLER SYSTEM |
MODEL |
CAPACITY 28°F GLYCOL 110°F COND 10°F SUBCOOL |
CAPACITY 33°F GLYCOL 110°F COND 10°F SUBCOOL |
PROCESS PUMP |
TANK CAPACITY (GAL) |
DIMENSIONS L X W X H (INCHES) |
208-230V /3PH /60HZ |
460V /3PH /60HZ |
GLYCOL FITTING CONNECTION SIZES |
| 120 HP |
PB430F28R4400-R |
768,400 |
868,000 |
10 HP |
400 |
184 X 94 X 86 |
471 Amps |
236 Amps |
Supply & Return Connections are 2 Inch |
| 160 HP |
PB440F40R4400-R |
1,152,000 |
1,300,000 |
10 HP |
400 |
227 X 94 X 86 |
713 Amps |
357 Amps |
| 200 HP |
PB450F56R4400-R |
1,364,000 |
1,544,000 |
10 HP |
400 |
234 X 94 X 86 |
849 Amps |
425 Amps |
|
|
|
|
|
|